MVWS deluge valve sets on the fire water header
NFPA 15

Fire Water Spray System

Open nozzles on dry pipework, released by a deluge valve on detection, that cool vessels and structures or control fires on transformers and process equipment.

At a glance

Governing standard
NFPA 15
Designed to
NFPA 15, OISD-STD-116, OISD-STD-117
Equipment source
Our own works

How it works

Schematic of a fire water spray system, showing how water, agent or signal flows through it

A water spray system holds a network of open, non-automatic nozzles on pipework that stays dry until the system is called. A separate detection line — a pilot sprinkler circuit, a linear heat cable or a flame detector — releases pressure from the deluge valve, the clapper opens fully and instantly, and water fills the network to every nozzle at once.

The distinction between medium and high velocity is the droplet, not the pressure. Medium velocity nozzles throw a wide cone of fine droplets that cool a surface and prevent it absorbing radiant heat from a fire nearby. High velocity nozzles throw heavier droplets hard enough to break the surface of a burning liquid and emulsify it, which is why they suit transformers and flammable liquid handling rather than exposure cooling.

Nozzle K-factor, spray angle and spacing follow from the surface being protected and the design density in litres per minute per square metre. A main pipeline strainer is required where the orifice is small enough to block.

Main components

  • The deluge valve with its trim.
  • Detection: a pilot sprinkler line, linear heat cable or flame detectors.
  • A strainer ahead of the nozzles.
  • Dry spray pipework and open nozzles aimed at the protected surfaces.

Testing and maintenance

  • Trip-test each deluge valve at the intervals the code sets, and reset it afterwards.
  • Run a full-flow test and check that every nozzle discharges and the pattern covers the equipment.
  • Clean the strainer after every test and discharge.
MVWS and HVWS
AspectMedium velocity (MVWS)High velocity (HVWS)
DropletFine, medium velocityCoarse, high velocity
PurposeCooling and exposure protection; fire controlExtinguishing oil fires by emulsifying the surface
Typical nozzle pressureAbout 1.4–3.5 barAbout 3.5–5 bar
Typical hazardsVessels, LPG spheres, cable trays, structuresTransformers, oil-filled equipment, lube oil systems

Typical pressures; the nozzle listing and the design govern.

Why De’s Technico

  • Equipment from our own catalogue

    Deluge valves, MVWS nozzles and strainers are made in our own works, so supply and execution answer to one schedule.

  • Built and tested in our works

    Manufactured in two factory units of 48,000 and 30,000 sq ft, with in-house testing before despatch.

  • 10 installations on record

    Our project record lists 10 medium and high velocity water spray installations, from design through commissioning.

  • One contract, design to handover

    A lump-sum turnkey scope on single-window responsibility: design, engineering, supply, installation and commissioning answer to one schedule.

Questions we are asked

MVWS or HVWS — which do we need?

MVWS cools and protects exposed surfaces such as vessels and structures; HVWS extinguishes oil fires on transformers and similar equipment by emulsifying the burning surface. Many sites use both.

Why is the pipework dry?

The nozzles are open, so the pipework stays dry until the deluge valve opens. That makes water spray suitable outdoors and in freezing conditions.

What releases the deluge valve?

A detection line — a pilot sprinkler line, linear heat cable or flame detectors — or a manual release. When it trips, the valve opens fully and water reaches every nozzle at once.

What density does a transformer need?

NFPA 15 sets 10.2 L/min/m² over the transformer and 6.1 L/min/m² over the non-absorbing ground around it.

Why is there a strainer before the nozzles?

Small nozzle orifices block easily. NFPA 15 calls for a strainer on systems with small orifices and where the water may carry debris.

Related systems

Track record

Projects with this system

All projects →

Considering us for a turnkey scope?

Send the hazard, the code and the site. Our engineers reply with a scheme and a price.