Foam fire fighting system installed at a tank farm
NFPA 11

Foam Based Fire Fighting System

Foam proportioned into the fire water and discharged over storage tanks, bunds and loading areas, where a burning flammable liquid has to be smothered rather than cooled.

At a glance

Governing standard
NFPA 11
Designed to
NFPA 11, NFPA 16, OISD-STD-116, OISD-STD-117
Equipment source
Our own works

How it works

Schematic of a foam based fire fighting system, showing how water, agent or signal flows through it

Foam works by floating a blanket over a burning liquid: it separates the fuel from the air, suppresses the vapour that is actually burning, and cools the surface underneath. The system has three jobs to do in order — proportion the concentrate into the water at the right ratio, carry the solution to the hazard, and aspirate it into finished foam at the discharge point.

Proportioning is done here with a bladder tank and ratio controller: water pressure squeezes an elastomeric bladder holding the concentrate, and the controller meters it into the stream across a wide range of flow without a concentrate pump. Discharge devices vary by hazard — foam chambers on a fixed roof tank, pourers over a floating roof, makers on a bund wall, and foam-water sprinklers overhead.

The ratio matters more than the volume. A system proportioning at 3% delivers a different blanket from one at 6%, and the concentrate has to match both the fuel and the discharge device.

Main components

  • The water supply, usually from the plant hydrant ring main.
  • The proportioner: a bladder tank with ratio controller, or an inline inductor.
  • Foam concentrate storage.
  • Solution mains to the protected hazards.
  • Discharge devices: foam makers, pourers and chambers on tanks, foam-water sprinklers, and monitors.

Testing and maintenance

  • Test proportioning at the intervals the code sets, checking the concentration of the solution produced.
  • Have a sample of the foam concentrate tested each year; it degrades in storage.
  • Inspect vapour seals on fixed-roof discharge devices, and flush the system after every discharge.
Proportioning methods
MethodHow it worksSuits
Bladder tank with ratio controllerWater pressure squeezes concentrate from a bladder into the ratio controllerMost fixed systems; no concentrate pump, wide flow range
Inline inductorA venturi draws concentrate into the water streamA single fixed discharge at constant flow
Balanced pressureA concentrate pump with a pressure-balancing valveLarge systems serving several hazards
PremixFoam solution stored ready-mixedSmall systems, such as rim seal protection
Expansion ratio
FoamExpansionTypical use
Low expansionUp to 20:1Storage tanks, spills, loading gantries
Medium expansion20:1 to 200:1Bunds, pits and trenches, vapour suppression
High expansionAbove 200:1Hangars, warehouses and enclosed spaces

Expansion ranges as NFPA 11 defines them.

Why De’s Technico

  • Equipment from our own catalogue

    Bladder tanks, ratio controllers, inductors, foam makers, pourers and chambers are made in our own works, so supply and execution answer to one schedule.

  • Built and tested in our works

    Manufactured in two factory units of 48,000 and 30,000 sq ft, with in-house testing before despatch.

  • 6 installations on record

    Our project record lists 6 foam system installations, from design through commissioning.

  • One contract, design to handover

    A lump-sum turnkey scope on single-window responsibility: design, engineering, supply, installation and commissioning answer to one schedule.

Questions we are asked

Why foam rather than water on a tank fire?

Most flammable liquids float on water and keep burning. Foam floats on the liquid instead, cutting off the air, suppressing the vapour that burns and cooling the surface.

What is the difference between 3% and 6% concentrate?

The proportion mixed into the water. A 3% concentrate needs half the storage of a 6% one for the same solution; the choice follows the concentrate’s listing and the hazard.

Do we need AR-AFFF or is AFFF enough?

Alcohol-resistant concentrate is needed for polar solvents such as alcohols and ketones, which break down ordinary foam. For hydrocarbons alone, AFFF is sufficient.

How long must a tank foam system run?

For fixed-roof tanks NFPA 11 sets 30 or 55 minutes depending on the flash point of the product; the design basis report states the figure for each tank.

Does foam concentrate expire?

It degrades in storage. A sample should be laboratory-tested every year, and the concentrate replaced when it falls out of specification.